The stainless steel water curtain sprinkler is a fire-fighting nozzle that forms a continuous water curtain barrier through dense water spray. It is designed for projects where the standard brass body is not the best fit — coastal installations, chemical plants, food processing areas, marine platforms and other wet or corrosive environments where a stainless steel wetted path extends service life and reduces maintenance.
Like all FUXEON® water curtain sprinklers, the stainless steel version is available in single-slot and double-slot types and is used to block the spread of fire, isolate heat radiation and toxic fumes, and substitute for a physical firewall where separation is not possible — large openings, passageways, stage prosceniums and the upper side of fire-resistant roller shutters.
Brass is the standard material for water curtain sprinklers and performs well in most indoor applications. Stainless steel becomes the better choice when the sprinkler is exposed to:
In these conditions a stainless steel body and deflector resist pitting and stress corrosion cracking, keeping the nozzle geometry — and therefore the water curtain pattern — stable over a longer service life.
Water curtain sprinklers are divided into two types according to fire protection method:
|
Type |
Working Principle |
Typical Use |
|
Fireproof water curtain |
A dense water wall directly blocks fire and smoke |
Large openings, passageways, stage prosceniums where a firewall cannot be built |
|
Protective cooling water curtain |
Water is sprayed onto the protected object; the water film cools it and raises its fire resistance |
Fire-resistant roller shutters, fire-resistant glass walls, doors and windows |
|
NO. |
Spray Point Height (m) |
Water Spray Intensity L/(s·m) |
Working Pressure (MPa) |
|
Fireproof water curtain |
≤12 |
2.0 |
0.1 |
|
Protective cooling water curtain |
≤4 |
0.5 |
0.1 |
If the spray point height of the protective cooling water curtain exceeds 4 meters, then for every 1 m increase, the spray intensity should increase by 0.1 L/(s·m).
|
Model |
K Flow |
Water Curtain Tilt Angle |
Water Curtain Spray Angle |
Structural Form |
Connection Thread |
Min. Working Pressure (MPa) |
|
ZSTM A-T28/175 |
28 |
0° |
175° |
Single Slot Type |
R1/2 |
0.10 |
|
ZSTM A-T40/175 |
40 |
0° |
175° |
Single Slot Type |
R1/2 |
0.10 |
|
ZSTM B-T28/160 |
28 |
90° |
160° |
Single Slot Type |
R1/2 |
0.10 |
|
ZSTM B-T40/160 |
40 |
90° |
160° |
Single Slot Type |
R1/2 |
0.10 |
|
ZSTM B-T60/160 |
60 |
90° |
160° |
Single Slot Type |
R1/2 |
0.10 |
|
ZSTM C-T40/160 |
40 |
90° |
160° |
Double Slot Type |
R1/2 |
0.10 |
|
ZSTM C-T60/160 |
60 |
90° |
160° |
Double Slot Type |
R1/2 |
0.10 |
Drencher sprinklers typically form a water curtain fire suppression system together with control valves, detection systems, alarm systems and piping systems. When a fire occurs, fire detectors or manual alarms trigger signals, opening control valves such as a deluge alarm valve or solenoid valve, starting the fire pump, and rapidly supplying high-pressure water to the sprinklers through the piping network. As the water flows through the nozzles, dense granular water droplets are sprayed in a predetermined direction, quickly forming a continuous water curtain or water wall.
Fire drencher systems should be installed at:
Our water curtain sprinkler has obtained China Fire Protection Product Certification (CCCF). Certificate details can be verified at www.cccf.com.cn. For the full document set, see our certificate page.
A: The standard range is precision-cast brass. Stainless steel can be specified for corrosive or wet environments; contact us with the model numbers and the exposure conditions so we can confirm availability and lead time.
A: No. The slot geometry, tilt angle and spray angle are the same as the brass version, so the hydraulic performance and coverage are unchanged. Only the material of the wetted parts differs.
A: Coastal and offshore sites, chemical and petrochemical plants, food and pharmaceutical washdown areas, and any location where chlorides or aggressive process fumes are present.
A: Yes. Both are rated at a minimum working pressure of 0.10 MPa and use the same R1/2 connection, so they can be combined in one water curtain line where different exposure conditions exist.
A: Inspect the slots for scale or debris, flush the line periodically, and check the deflector for mechanical damage. Stainless steel resists corrosion but does not resist blockage, so flushing remains important.
A: Yes. We support brand customization and can produce other text content on request. See the inquiry page to discuss OEM requirements.
Specifying a stainless steel water curtain sprinkler for a corrosive or coastal project?