Engineered for critical asset protection, the FM200 Gas Fire Extinguishing System delivers rapid, residue-free fire suppression using heptafluoropropane as its clean agent. This solution is widely adopted in data centers, telecommunication facilities, and archive rooms where water-based suppression would cause irreversible damage. The system reaches extinguishing concentrations within 10 seconds, effectively interrupting the chemical chain reaction of combustion while maintaining safe oxygen levels for momentary human exposure.
FM200 Clean Agent Fire Suppression System operates through a pressurized agent storage configuration, releasing gas via a fixed-pipe network and discharge nozzles engineered for uniform distribution. Its zero ozone depletion potential and short atmospheric lifetime meet stringent environmental regulations, while occupying minimal floor space compared to inert gas alternatives. The pre-engineered cylinder assemblies pair with detection and control panels to form a complete, self-contained suppression unit.
| Technical Parameters | |
|---|---|
| Molecular Weight | 170.03 g/mol |
| Boiling Point | -16.4°C (2.5°F) |
| Vapor Pressure at 20°C | 58.8 psi (405 kPa) |
| Liquid Density at 20°C | 1.40 g/cm³ |
| Design Concentration (Class A) | 6.7–7.2% by volume |
| Design Concentration (Class B) | 8.7–9.0% by volume |
| Nozzle Working Pressure | 29–146 psi (2–10 bar) |
| Storage Pressure at 21°C | 360 psi (25 bar) or 600 psi (42 bar) |
| Cylinder Volumes Available | 10 lb to 1000 lb agent capacity |
| Temperature Operating Range | 0°C to 54°C (32°F to 130°F) |
| Material Compatibility | Suitable for electronics, paper, and fine arts |
| Electrical Non-Conductivity | Confirmed per ASTM test methods |
Common enclosures protected by FM200 Clean Agent Fire Suppression System include server racks, tape libraries, power distribution units, and flammable liquid storage cabinets. Post-discharge cleanup is eliminated, ensuring business continuity with minimal operational downtime.